GwLin Changelog: Difference between revisions
		
		
		
		
		
		Jump to navigation
		Jump to search
		
				
		
		
	
No edit summary  | 
				No edit summary  | 
				||
| (153 intermediate revisions by 6 users not shown) | |||
| Line 1: | Line 1: | ||
= Info below not updated anymore, see redmine roadmap for latest data =  | |||
<div style="padding: 5px; margin: 0.50em 0; background-color: #FFDDDD; border: thin solid #DDBBBB; overflow: hidden;">  | |||
'''Warning:'''  | |||
Last update below was for 2.0.156 (03.04.2020)  | |||
</div>  | |||
= TELEM-AGC, TELEM-GW6e, TELEM-GWM53 and TELEM-GWM25 =  | |||
== Recommended software ==  | |||
<div style="padding: 5px; margin: 0.50em 0; background-color: #FFDDDD; border: thin solid #DDBBBB; overflow: hidden;">  | |||
'''Warning! GWS >= 2142 must be used'''  | |||
</div>  | |||
=== kernel4: ===  | |||
2.0.156-3e1f29e-k4 - GW6e VMX53/6DL, AGC 6DL/6UL  | |||
2.0.156-3e1f29e-k4-03 - GWM VMX25/VMX53/6DL/6UL  | |||
=== kernel2(pre 2014 devices): ===  | |||
2020.04.01-next-02-c8fd29a - GW6e ('''No IEC61850 Client''')  | |||
== Firmware downgrade ==  | |||
<div style="padding: 5px; margin: 0.50em 0; background-color: #FFDDDD; border: thin solid #DDBBBB; overflow: hidden;">  | |||
'''Warning:'''  | |||
* Downgrading firmware has never been supported.  | |||
* It is possible to downgrade, but there are no guarantees.  | |||
</div>  | |||
==  telem-app Changelog for kernel 4  ==  | |||
*2.0.156-3e1f29e-k4/2.0.156-3e1f29e-k4-03 (GWS 2142)  | |||
: IEC61850 | IEC 61850 Client KEMA certified  | |||
: IEC60870 | 104 Server KEMA certified  | |||
: IEC60870 | 101UB Server fix AI event sent as normalized when implied float  | |||
: IEC60870 | FIX AO subtype determination  | |||
: IEC60870 | Fix DO/AO unknown COT  | |||
: IEC60870 | 101B Server fix floating point subtype up  | |||
: IEC60870 | Fix deact in client  | |||
: IEC60870 | Fix multiple lower level addresses per device (fix #3450)  | |||
: IEC60870 | DO/AO fixes  | |||
: OPC UA | OPC UA Server implementation  | |||
: Api | Add cls.json to webserver (fix #3522)  | |||
: Db | Fix backup import  | |||
: Core | Boost 1.71  | |||
: Core | Sensor code safer  | |||
: Core | Sensor objects have flags  | |||
: Core | AGC SCL IO  | |||
: ModBus | Mitigate offset in value<->data (fix #3462)  | |||
: ModBus | Initial impl of 64 bit ai type (fix #3402)  | |||
*2.0.141-3b46188-k4-02  Telem-GWM (GWS 2133)   | |||
: Core | Fixed Control issues   | |||
: Logging | PCAP feature    | |||
*2.0.141-3b46188-k4  Telem-AGC, Telem-GW6e (GWS 2133)  | |||
: Core | Fixed Control issues    | |||
: Logging | PCAP feature    | |||
*2.0.132-ddea1dd-k4-02  Telem-AGC, Telem-GW6e (GWS 2131)  | |||
: Core | Fixed Select event loss issue    | |||
: Logging | Improved logging    | |||
*2.0.132-ddea1dd-k4-03  Telem-GWM (GWS 2131)   | |||
: Core | Fixed Select event loss issue   | |||
: Logging | Improved logging    | |||
*2.0.82-288715d-k4  Telem-GW6e, Telem-GWM (GWS 2104)    | |||
: Updates | Minor bug fixes  | |||
*2018.02.08-linux_4-04-b7d1941 / 2018.02.08-next-02-1a34917 (GWS 2086)  | |||
: Formula | Fix complex formulas not recalculating after after init  | |||
*2018.01.12-linux_4-01-8b72574 / 2018.01.12-next-02-abe5e00 (GWS 2083)  | |||
: Formula | DB accessor thread optimisations  | |||
: Change Filter | Discard NaN values. Pass event with previous value and OVF bit  | |||
: IEC60870 | Event priority rework  | |||
: Core | Periodical GI improvements  | |||
: IEC61850 | Alstom P14 DI bug workaround [https://phobos.martem.ee/redmine/issues/2916 #2916]  | |||
: IEC61850 | Improve cmds [https://phobos.martem.ee/redmine/issues/2925 #2925]  | |||
: IEC101UB Slave | Improve varLenMsg parsing [https://phobos.martem.ee/redmine/issues/2933 #2933]  | |||
: IEC101/104 | Add debug messages to AO cmd  | |||
: Scale Filter | Fix AI scaling twice on lower device timeout [https://phobos.martem.ee/redmine/issues/2930 #2930]  | |||
*2017.11.18-linux_4-01-87d4416 / 2017.11.18-next-01-9c9c97b (GWS 2081b)  | |||
: Build for all devices and kernels  | |||
* 2017.11.10-linux_4-01-8595646 / N/A k2 (GWS 2081b)  | |||
: Formula | Integral expression minor timing fix [https://phobos.martem.ee/redmine/issues/2848 #2848]  | |||
: IEC60870 | Fix device objects not sent with GI on 101-104 translation, only lower device objects [https://phobos.martem.ee/redmine/issues/2908 #2908]   | |||
* 2017.10.31-linux_4-03-e9d281f / N/A k2 (GWS 2081b)  | |||
: Formula | Integral expression rewrite to integral(@ai, @di) [https://phobos.martem.ee/redmine/issues/2848 #2848]  | |||
: Filter | Optimize lock usage between LatestValues and UpdateLatest  | |||
== telem-app Changelog for kernel 2 ==  | |||
* 2018.02.08-next-02-1a34917  | |||
: Formula | Fix complex formulas not recalculating after after init  | |||
: Other fixes  | |||
* 2017.09.26-next-03-c81082e / 2017.09.26-linux_4-05-50ff00d (GWS 2079)  | |||
: '''HOTFIX''' IEC101/104 DO_FN | Fix: SCADA did not receive command status responses if DO_FN object configured for IED [https://phobos.martem.ee/redmine/issues/2877 #2871]  | |||
* 2017.09.20-next-01-b162ac5 / 2017.09.20-linux_4-02-2436894 (GWS 2079)  | |||
: Modbus | Polling sequence fix (AI was polled less) [https://phobos.martem.ee/redmine/issues/2871 #2871]  | |||
: Modbus | Communication on port stalls if any device has no valid objects [https://phobos.martem.ee/redmine/issues/2873 #2873]  | |||
* 2017.09.13-next-01-800b844 / 2017.09.13-linux_4-feature-integral-expression-01-930dddd (GWS 2079)  | |||
: Modbus | fix AO scaling [https://phobos.martem.ee/redmine/issues/2807 #2807]  | |||
* 2017.09.11-linux_4-01-7ee57df (GWS 2079)  | |||
: Telem Master | support 18 (was 17) CMD address  | |||
: Formula | AI Formula -> AO CMD fix  | |||
* 2017.08.08 (GWS 2079)  | |||
: WebServer | Correctly set persistant pages  | |||
: WebServer | Fix user credentials  | |||
: GWM IO-Board IFR feature [https://phobos.martem.ee/redmine/issues/2841 #2841]  | |||
: Modbus | Fix polling delay [https://phobos.martem.ee/redmine/issues/2839 #2839]  | |||
: WebServer | fix sprintf buffer size  | |||
: Channel | Channel optimisations  | |||
: Core | Fix thread pool manager (TaskIoBase)  | |||
: WebServer | replace deprecated functions  | |||
: IEC101/104 | add DST bit functionality [https://phobos.martem.ee/redmine/issues/2833 #2833]  | |||
* 2017.06.09-next-01-353984f (GWS 2079)  | |||
: Reset 2 Clear Buffers fix [https://phobos.martem.ee/redmine/issues/2814 #2814]  | |||
* 2017.04.17-next-08-af772c0  | |||
: Logging | Buffered logging  | |||
* 2017.04.05-next-07-65a2e5a  | |||
: SPA-Bus | Timesync: send 3x short ts and 3x long ts  | |||
* 2017.04.03-next-01-557bc40  | |||
: Core | Fix spontaneous events after GI on initial successful lower lever device initialisation ([https://phobos.martem.ee/redmine/issues/2793 #2793])  | |||
: Core | Refix sending reset cmds from TDC  | |||
* 2017.03.21-next-03-b5cc1d0  | |||
: Optimisation (Webserver) | Avoid websocket connection duplicates  | |||
: Optimisation (app close) | make WebSocketAppender thread safe  | |||
: Optimisation (app close) | fix numerous potential places that cause segfault on app close  | |||
: Build | build with latest GNU compilers (v 6).  | |||
: IEC60870 | IEC103 events without timetag fix  | |||
: Formula | fix Formula output controller trying to execute DO CMD until it succeeds.  | |||
: Formula | fix Formula when using another formula object as argument, that is further down the list in GWS ([https://phobos.martem.ee/redmine/issues/2794 #2794])  | |||
* 2017.01.31-next-01-3eefdf3  | |||
: Optimisation | all telem-app optimisations merge  | |||
: IEC60870 | fix control state conatiner in IEC 101 for GWM with IO board  | |||
: Protocol | control state logger improved logs  | |||
* 2016.12.02-next-01-a502dae '''Don't use on VMX25''' '''Don't use on GWM with DO'''  | |||
: SPA-Bus | ABB SPAC330C feature  | |||
: IEC61850 | 101 support multiple DO with same v-addresses (multiple rows with same v-addresses)  | |||
* 2016.11.23-next-01-0260688 '''Don't use on VMX25''' '''Don't use on GWM with DO'''  | |||
: IEC61850 | 103 support multiple DO with same v-addresses (multiple rows with same v-addresses)  | |||
* 2016.11.15-next-02-b43c191 '''Don't use on VMX25''' '''Don't use on GWM with DO'''  | |||
: Localization | Change non-ASCII characters to * in Port and Device commments ([https://phobos.martem.ee/redmine/issues/2751 #2751])  | |||
* 2016.11.15-next-01-5dc3aa7 '''Don't use on VMX25''' '''Don't use on GWM with DO'''  | |||
: IEC61850 | 104 event loss after disconnect fix ([https://phobos.martem.ee/redmine/issues/2725 #2725])  | |||
* 2016.11.04-next-02-3a9808a '''Don't use on VMX25''' '''Don't use on GWM with DO'''  | |||
: Database | Set object flags to Invalid instead of NotTopical on startup  | |||
: SPA-Bus | objects not going not topical on Timeout fix  | |||
: SPA-Bus | potential segfault fix  | |||
* 2016.10.08-next-01-c91481f  | |||
: IEC-101,104 | GI Switch per object (requires GWS 6.1.0.2068+)  | |||
: IEC-101,104 | DO can have 2 downstream addresses (like 1/2)  | |||
* 2016.10.05-next-06-bb13408  | |||
: Protocol | Remove event sorting by time when sending to upstream '''Retract 2016.09.19-next-01-c0127ec additions'''  | |||
: Protocol | upstream events faster  | |||
: IEC-103 | Micom workarounds  | |||
* 2016.10.03-next-02-1cb7e5f  | |||
: Protocol | time sync interval from XML implementation  | |||
: SPA-Bus | fix event time is it is assumed that event came before last minut change  | |||
: SPA-Bus | request L, then poll once and change device  | |||
: SPA-Bus | delay next device for 50ms after timesync  | |||
* 2016.09.26-next-01-91e178f  | |||
: SPA-Bus | Scaling fix ([https://phobos.martem.ee/redmine/issues/2689 #2689])  | |||
: Logging | raw port log in ASCII  | |||
* 2016.09.23-next-01-00fde37 ([https://phobos.martem.ee/redmine/issues/2721 #2721])  | |||
: SPA-Bus | event can have effect on multiple objects  | |||
* 2016.09.19-next-01-c0127ec ([https://phobos.martem.ee/redmine/issues/2693 #2693])  | |||
: Protocol | Events are sent upstream in order of the lowest timetag '''Retracted in 2016.10.05-next-06-bb13408'''  | |||
* 2016.09.08-next-01-526b387   | |||
: IEC | fix IEC 101 UB variable length frame bigger than 255 issue  | |||
: Formula | fix double masking in fomrula ???  | |||
* 2016 year device fw and GWS 6.1.0.2064  | |||
: NoMainLog for formula  | |||
* 2016.08.25-next-03-b45984d  | |||
: Modbus | ai_bit DI type  | |||
: Modbus | DO: define ON and OFF address in the same cell  | |||
: improved logging  | |||
: SPA-Bus | poll all  | |||
* 2016.08.23-next-01-d702b81  | |||
: Logging | fine tuned device initialization logging. Old device oriented (GW6, RTA)  | |||
: fix DO Inversion bug ([https://phobos.martem.ee/redmine/issues/2702 #2702])  | |||
* 2016.05.11-next-02-e02304a  | |||
:SPA-Bus | minor fixes for rare nack and timeout cases  | |||
:SPA-Bus | commented out object sorting  | |||
* 2016.05.04-next-01-64e4492  | |||
:SPA-Bus | protocol subtype for ABB ref542  | |||
:SPA-Bus | poll L messages after 5 object poll requests  | |||
:SPA-Bus | mode 1 implementation: poll multiple objects in one request ([https://phobos.martem.ee/redmine/issues/2635 #2635])  | |||
:SPA-Bus | DO: define ON and OFF address in the same cell   | |||
:SPA-Bus | channel number definable for every event number ([https://phobos.martem.ee/redmine/issues/2637 #2637])  | |||
:SPA-Bus | event numbers for Intermediate and Error states  | |||
:SPA-Bus | fallback fixes ([https://phobos.martem.ee/redmine/issues/2658 #2658])  | |||
:SPA-Bus | switch between devices on same port after L message  | |||
:SPA-Bus | define incoming DI object type (Dobule/Single) ([https://phobos.martem.ee/redmine/issues/2654 #2654])  | |||
:SD card licence implementation ([https://phobos.martem.ee/redmine/issues/2592 #2592])  | |||
:remove non ASCII characters from object comment ([https://phobos.martem.ee/redmine/issues/2577 #2577])  | |||
*[22.03.2016]  | |||
:1-wire segfault on bing temp. change fix ([https://phobos.martem.ee/redmine/issues/2640 #2640])  | |||
*[11.03.2016]  | |||
:IEC-104 object type priorities fix. Big amounts of AI data prevented DI events propagation. ([https://phobos.martem.ee/redmine/issues/2625 #2625])  | |||
*[23.02.2016]  | |||
:webserver v2 IE11 not working fix  | |||
*[10.02.2016]  | |||
:NEW_DATABASE formulas numerous fixes  | |||
:ADDED LIB TO PROJECT: fastformat  | |||
:logging optimizations using fastformat. VMX25 up to 10x faster  | |||
*[16.12.2015]  | |||
:license additions to support no modem GWM ([https://phobos.martem.ee/redmine/issues/2565 #2565])  | |||
*[17.11.2015]  | |||
:longer interval for some tasks  | |||
:SyncDatabaseToFile 2s->5s  | |||
:ProcessRetranslation 10ms->500ms  | |||
:explicitly sync db backup to non-volatile memory only on reset/low-power.  | |||
*[06.11.2015]  | |||
:IEC-101/104 QOC (Qualifier of command) implementation ([https://phobos.martem.ee/redmine/issues/2495 #2495])  | |||
*[05.11.2015]  | |||
:AI scaling rewrite '''(COMPATIBILITY BREAK)'''  | |||
:virtual I/O object pair crash app if invalid address fix ([https://phobos.martem.ee/redmine/issues/2572 #2572])  | |||
*[30.10.2015]  | |||
:web-server v2 shows device eth info ([https://phobos.martem.ee/redmine/issues/2532 #2532])  | |||
*[16.10.2015]  | |||
:fix SPA-Bus polling delay ([https://phobos.martem.ee/redmine/issues/2546 #2546])  | |||
*[14.10.2015]  | |||
:IEC DO_FN | IEC101/104 type 105 C_RP_NA_1 (reset process) implementation ([https://phobos.martem.ee/redmine/issues/2498 #2498])  | |||
:IEC DO_FN | IEC101/104 GI command via DO implementation ([https://phobos.martem.ee/redmine/issues/2499 #2499])  | |||
*[13.10.2015]  | |||
:zero value deadband implementation ([https://phobos.martem.ee/redmine/issues/2536 #2536])  | |||
*[24.09.2015]  | |||
:DO/AO stops IEC-101 messages fix for devices using old database ([https://phobos.martem.ee/redmine/issues/2527 #2527])  | |||
:allow bigger conf size for NEW_DATABASE devices  | |||
:SETUP_WITH_XML_BIN_SIZE 500KB->1.5MB  | |||
:EXTRACTED_XML_SETUP_SIZE 6MB->20MB  | |||
*[07.09.2015]  | |||
:GWM IO-board + 101-104 conversion not working fix ([https://phobos.martem.ee/redmine/issues/2520 #2520])  | |||
*[25.08.2015]  | |||
:IEC-61850 mem-leak/consumption fixes  | |||
:remove BIT_INVALID_TIME from BIT_VALUE_CHANGED_MASK  | |||
*[22.08.2015]  | |||
:devie booting time nnX times faster ([https://phobos.martem.ee/redmine/issues/2472 #2472])  | |||
== kernel 4 Changelog since 2017 ==  | |||
*2017.08.22  | |||
: fix GW DNS service  | |||
*2017.02.10  | |||
: fix sftp access  | |||
: fix configuring SSH from GWS  | |||
== kernel 2 Changelog since 2013 ==  | |||
* 2017.07.12  | |||
: log4cxx | patch for socket appender  | |||
: pack_logs | pack modem history log  | |||
: init | fix spamming logs (S48, S61m S99)  | |||
: fw_update | fix errors on fw update (S12usb)  | |||
: init | fix spamming logs on stop (S37)  | |||
: modem | fix handling huawei modems  | |||
: WebServer | Restore syslog options  | |||
* 2017.04.17-next-08-af772c0  | |||
: update | Additional checks in post-update scripts for GWM rev.1 FTDI IO Board  | |||
* 2017.04.05-next-07-65a2e5a  | |||
: pack_logs now packs all existing console logs and eeprom log if exists  | |||
* 2017.04.03-next-03-49423a0  | |||
: fix enabling peripheral power on startup with usbs suspended (fixes old GWM53 FTDI IO Board)  | |||
* 2017.01.31-next-01-3eefdf3  | |||
: remove cifs support from vmx25 kernel. No more space left on device.  | |||
* 2016.11.04-next-01-51a8c40 '''Don't use on VMX25''' '''Don't use on GWM with DO'''  | |||
: IEC-101,104 | DO invert fix sending ACK with inverted address  | |||
: init | S99phy fix toggling LAN power and wait longer  | |||
: init | fix starting modem then date is in the start of epoch (1970)  | |||
: init | Script fixes for fresh device with linux default time  | |||
* 2016.10.19-next-09-3e89e79 '''Don't use on VMX25''' '''Don't use on GWM with DO'''  | |||
: CIFS support in kernel for network mounts '''!! This change bricks VMX25. Removed from VMX25 after 30.01.2017'''  | |||
* 2016.10.08-next-01-c91481f  | |||
: init | optimizations for FTDI eeprom software  | |||
: init | getwdbootmsg fixes  | |||
: init | major refactoring. Performance & readability fixes  | |||
* 2016.10.03-next-02-1cb7e5f  | |||
: Syslog | Add possibility to change loglevel and remote server port  | |||
: ntp | do not restart ntp if only gps is configured (2711)  | |||
: ntp | avoid frequent ntp restarts by other scripts  | |||
: modem | avoid frequent modem restart by multiple scripts (only 1 restart allowed per one minute).  | |||
: modem | rewrite telit modem reseting as described in telit manual  | |||
: init | fix socat sometimes creating /dev/tty* as ordinary file instead of letting modem driver to do it.  | |||
: init | performance fixes  | |||
* 2016.07.28-next-06-3d426af  | |||
:Device CPU frequency lowered from 1.2GHz to 1.0GHz | Improved ssh key generation and license cheking  | |||
*[11.02.2016]  | |||
:physical interface checker script implementation  | |||
*[10.02.2016]  | |||
:ADDED LIB TO PROJECT: fastformat  | |||
*[26.01.2016]  | |||
:GWS 'Get logs' acquires n+1 more rotating logs  | |||
*[23.07.2015]  | |||
:ADDED LIB TO PROJECT: boost_chrono to source.pro (websocketpp 0.6.0 depends)  | |||
*[08.06.2015]  | |||
:application segmentation fault fix (2429)  | |||
*[27.04.2015]  | |||
:DI fallback bug fix (2312)  | |||
*[23.04.2015]  | |||
:DI object double inversion bug fix (2345)  | |||
*[21.04.2015]  | |||
:no flags not working fix (2194)  | |||
*[24.03.2015]  | |||
:Periodical GI implementation for all protocols (every 5th minute of hour)  | |||
*[16.03.2015]  | |||
:Telem Master protocol implementation  | |||
*[29.01.2015]  | |||
:IEC-10x ASDU transfer implementation  | |||
*[30.10.2014]  | |||
:IEC-101B serial communication improvements  | |||
*[23.10.2014]  | |||
:No main/CSV log for individual objects  | |||
*2014.01.13-next-01-2a5df30  | |||
:added uINT16 (unsigned 16bit integer) in modbus protocol. (also update gws)  | |||
*2014.01.09-next-01-2fae2d9  | |||
:fix IEC104 bug in GW6  | |||
*2014.01.07-next-01-8180155  | |||
:fix fallback (GW6e and GWM), "NONE" protocol, device "in use"=no, FP-to-normalised conversion, deadband issues, IEC104 bug in GW6e. (also update gws)  | |||
*2013.11.18-next-04  | |||
:fix IEC-104 bug (mark data as NT if connection to IEC-104 slave is lost and parameter "failed query count for disabling contr." > 1)  | |||
*2013.11.12-next01  | |||
:fix AO feedback bug in GW6 and RTA-A  | |||
*2013.11.04-next      | |||
:time invalid flag for GW6 and RTA-A (also requires DSP/RTC software update!)  | |||
*2013.10.24-next      | |||
:IEC101-to-IEC104 short time to long time conversion  | |||
*2013.09.16-next07    | |||
:configurable COT=2 Bytes for IEC101b  | |||
*2013.09.09-next01    | |||
:configurable COT=2 Bytes for IEC101ub  | |||
*2013.07.12-next02    | |||
:write modem status to /var/log/modem.st  | |||
= Old Devices RTA-A and GW6 =  | |||
== Latest Firmware ==  | |||
Last fw version GW6: 2015.12.11-develop-01-104a492  | |||
Last fw version RTA-A M502: 2015.12.11-develop-01-104a492  | |||
Last fw version RTA-A M501: 2015.12.11-develop-01-104a492  | |||
==GW6-1206 ==  | ==GW6-1206 ==  | ||
* Timezones for ports and system.  | * Timezones for ports and system.  | ||
Latest revision as of 10:11, 2 July 2021
Info below not updated anymore, see redmine roadmap for latest data
TELEM-AGC, TELEM-GW6e, TELEM-GWM53 and TELEM-GWM25
Recommended software
kernel4:
2.0.156-3e1f29e-k4 - GW6e VMX53/6DL, AGC 6DL/6UL
2.0.156-3e1f29e-k4-03 - GWM VMX25/VMX53/6DL/6UL
kernel2(pre 2014 devices):
2020.04.01-next-02-c8fd29a - GW6e (No IEC61850 Client)
Firmware downgrade
telem-app Changelog for kernel 4
- 2.0.156-3e1f29e-k4/2.0.156-3e1f29e-k4-03 (GWS 2142)
 
- IEC61850 | IEC 61850 Client KEMA certified
 - IEC60870 | 104 Server KEMA certified
 - IEC60870 | 101UB Server fix AI event sent as normalized when implied float
 - IEC60870 | FIX AO subtype determination
 - IEC60870 | Fix DO/AO unknown COT
 - IEC60870 | 101B Server fix floating point subtype up
 - IEC60870 | Fix deact in client
 - IEC60870 | Fix multiple lower level addresses per device (fix #3450)
 - IEC60870 | DO/AO fixes
 - OPC UA | OPC UA Server implementation
 - Api | Add cls.json to webserver (fix #3522)
 - Db | Fix backup import
 - Core | Boost 1.71
 - Core | Sensor code safer
 - Core | Sensor objects have flags
 - Core | AGC SCL IO
 - ModBus | Mitigate offset in value<->data (fix #3462)
 - ModBus | Initial impl of 64 bit ai type (fix #3402)
 
- 2.0.141-3b46188-k4-02 Telem-GWM (GWS 2133)
 
- Core | Fixed Control issues
 - Logging | PCAP feature
 
- 2.0.141-3b46188-k4 Telem-AGC, Telem-GW6e (GWS 2133)
 
- Core | Fixed Control issues
 - Logging | PCAP feature
 
- 2.0.132-ddea1dd-k4-02 Telem-AGC, Telem-GW6e (GWS 2131)
 
- Core | Fixed Select event loss issue
 - Logging | Improved logging
 
- 2.0.132-ddea1dd-k4-03 Telem-GWM (GWS 2131)
 
- Core | Fixed Select event loss issue
 - Logging | Improved logging
 
- 2.0.82-288715d-k4 Telem-GW6e, Telem-GWM (GWS 2104)
 
- Updates | Minor bug fixes
 
- 2018.02.08-linux_4-04-b7d1941 / 2018.02.08-next-02-1a34917 (GWS 2086)
 
- Formula | Fix complex formulas not recalculating after after init
 
- 2018.01.12-linux_4-01-8b72574 / 2018.01.12-next-02-abe5e00 (GWS 2083)
 
- Formula | DB accessor thread optimisations
 - Change Filter | Discard NaN values. Pass event with previous value and OVF bit
 - IEC60870 | Event priority rework
 - Core | Periodical GI improvements
 - IEC61850 | Alstom P14 DI bug workaround #2916
 - IEC61850 | Improve cmds #2925
 - IEC101UB Slave | Improve varLenMsg parsing #2933
 - IEC101/104 | Add debug messages to AO cmd
 - Scale Filter | Fix AI scaling twice on lower device timeout #2930
 
- 2017.11.18-linux_4-01-87d4416 / 2017.11.18-next-01-9c9c97b (GWS 2081b)
 
- Build for all devices and kernels
 
- 2017.11.10-linux_4-01-8595646 / N/A k2 (GWS 2081b)
 
- Formula | Integral expression minor timing fix #2848
 - IEC60870 | Fix device objects not sent with GI on 101-104 translation, only lower device objects #2908
 
- 2017.10.31-linux_4-03-e9d281f / N/A k2 (GWS 2081b)
 
- Formula | Integral expression rewrite to integral(@ai, @di) #2848
 - Filter | Optimize lock usage between LatestValues and UpdateLatest
 
telem-app Changelog for kernel 2
- 2018.02.08-next-02-1a34917
 
- Formula | Fix complex formulas not recalculating after after init
 - Other fixes
 
- 2017.09.26-next-03-c81082e / 2017.09.26-linux_4-05-50ff00d (GWS 2079)
 
- HOTFIX IEC101/104 DO_FN | Fix: SCADA did not receive command status responses if DO_FN object configured for IED #2871
 
- 2017.09.20-next-01-b162ac5 / 2017.09.20-linux_4-02-2436894 (GWS 2079)
 
- Modbus | Polling sequence fix (AI was polled less) #2871
 - Modbus | Communication on port stalls if any device has no valid objects #2873
 
- 2017.09.13-next-01-800b844 / 2017.09.13-linux_4-feature-integral-expression-01-930dddd (GWS 2079)
 
- Modbus | fix AO scaling #2807
 
- 2017.09.11-linux_4-01-7ee57df (GWS 2079)
 
- Telem Master | support 18 (was 17) CMD address
 - Formula | AI Formula -> AO CMD fix
 
- 2017.08.08 (GWS 2079)
 
- WebServer | Correctly set persistant pages
 - WebServer | Fix user credentials
 - GWM IO-Board IFR feature #2841
 - Modbus | Fix polling delay #2839
 - WebServer | fix sprintf buffer size
 - Channel | Channel optimisations
 - Core | Fix thread pool manager (TaskIoBase)
 - WebServer | replace deprecated functions
 - IEC101/104 | add DST bit functionality #2833
 
- 2017.06.09-next-01-353984f (GWS 2079)
 
- Reset 2 Clear Buffers fix #2814
 
- 2017.04.17-next-08-af772c0
 
- Logging | Buffered logging
 
- 2017.04.05-next-07-65a2e5a
 
- SPA-Bus | Timesync: send 3x short ts and 3x long ts
 
- 2017.04.03-next-01-557bc40
 
- Core | Fix spontaneous events after GI on initial successful lower lever device initialisation (#2793)
 - Core | Refix sending reset cmds from TDC
 
- 2017.03.21-next-03-b5cc1d0
 
- Optimisation (Webserver) | Avoid websocket connection duplicates
 - Optimisation (app close) | make WebSocketAppender thread safe
 - Optimisation (app close) | fix numerous potential places that cause segfault on app close
 - Build | build with latest GNU compilers (v 6).
 - IEC60870 | IEC103 events without timetag fix
 - Formula | fix Formula output controller trying to execute DO CMD until it succeeds.
 - Formula | fix Formula when using another formula object as argument, that is further down the list in GWS (#2794)
 
- 2017.01.31-next-01-3eefdf3
 
- Optimisation | all telem-app optimisations merge
 - IEC60870 | fix control state conatiner in IEC 101 for GWM with IO board
 - Protocol | control state logger improved logs
 
- 2016.12.02-next-01-a502dae Don't use on VMX25 Don't use on GWM with DO
 
- SPA-Bus | ABB SPAC330C feature
 - IEC61850 | 101 support multiple DO with same v-addresses (multiple rows with same v-addresses)
 
- 2016.11.23-next-01-0260688 Don't use on VMX25 Don't use on GWM with DO
 
- IEC61850 | 103 support multiple DO with same v-addresses (multiple rows with same v-addresses)
 
- 2016.11.15-next-02-b43c191 Don't use on VMX25 Don't use on GWM with DO
 
- Localization | Change non-ASCII characters to * in Port and Device commments (#2751)
 
- 2016.11.15-next-01-5dc3aa7 Don't use on VMX25 Don't use on GWM with DO
 
- IEC61850 | 104 event loss after disconnect fix (#2725)
 
- 2016.11.04-next-02-3a9808a Don't use on VMX25 Don't use on GWM with DO
 
- Database | Set object flags to Invalid instead of NotTopical on startup
 - SPA-Bus | objects not going not topical on Timeout fix
 - SPA-Bus | potential segfault fix
 
- 2016.10.08-next-01-c91481f
 
- IEC-101,104 | GI Switch per object (requires GWS 6.1.0.2068+)
 - IEC-101,104 | DO can have 2 downstream addresses (like 1/2)
 
- 2016.10.05-next-06-bb13408
 
- Protocol | Remove event sorting by time when sending to upstream Retract 2016.09.19-next-01-c0127ec additions
 - Protocol | upstream events faster
 - IEC-103 | Micom workarounds
 
- 2016.10.03-next-02-1cb7e5f
 
- Protocol | time sync interval from XML implementation
 - SPA-Bus | fix event time is it is assumed that event came before last minut change
 - SPA-Bus | request L, then poll once and change device
 - SPA-Bus | delay next device for 50ms after timesync
 
- 2016.09.26-next-01-91e178f
 
- SPA-Bus | Scaling fix (#2689)
 - Logging | raw port log in ASCII
 
- 2016.09.23-next-01-00fde37 (#2721)
 
- SPA-Bus | event can have effect on multiple objects
 
- 2016.09.19-next-01-c0127ec (#2693)
 
- Protocol | Events are sent upstream in order of the lowest timetag Retracted in 2016.10.05-next-06-bb13408
 
- 2016.09.08-next-01-526b387
 
- IEC | fix IEC 101 UB variable length frame bigger than 255 issue
 - Formula | fix double masking in fomrula ???
 
- 2016 year device fw and GWS 6.1.0.2064
 
- NoMainLog for formula
 
- 2016.08.25-next-03-b45984d
 
- Modbus | ai_bit DI type
 - Modbus | DO: define ON and OFF address in the same cell
 - improved logging
 - SPA-Bus | poll all
 
- 2016.08.23-next-01-d702b81
 
- Logging | fine tuned device initialization logging. Old device oriented (GW6, RTA)
 - fix DO Inversion bug (#2702)
 
- 2016.05.11-next-02-e02304a
 
- SPA-Bus | minor fixes for rare nack and timeout cases
 - SPA-Bus | commented out object sorting
 
- 2016.05.04-next-01-64e4492
 
- SPA-Bus | protocol subtype for ABB ref542
 - SPA-Bus | poll L messages after 5 object poll requests
 - SPA-Bus | mode 1 implementation: poll multiple objects in one request (#2635)
 - SPA-Bus | DO: define ON and OFF address in the same cell
 - SPA-Bus | channel number definable for every event number (#2637)
 - SPA-Bus | event numbers for Intermediate and Error states
 - SPA-Bus | fallback fixes (#2658)
 - SPA-Bus | switch between devices on same port after L message
 - SPA-Bus | define incoming DI object type (Dobule/Single) (#2654)
 - SD card licence implementation (#2592)
 - remove non ASCII characters from object comment (#2577)
 
- [22.03.2016]
 
- 1-wire segfault on bing temp. change fix (#2640)
 
- [11.03.2016]
 
- IEC-104 object type priorities fix. Big amounts of AI data prevented DI events propagation. (#2625)
 
- [23.02.2016]
 
- webserver v2 IE11 not working fix
 
- [10.02.2016]
 
- NEW_DATABASE formulas numerous fixes
 - ADDED LIB TO PROJECT: fastformat
 - logging optimizations using fastformat. VMX25 up to 10x faster
 
- [16.12.2015]
 
- license additions to support no modem GWM (#2565)
 
- [17.11.2015]
 
- longer interval for some tasks
 - SyncDatabaseToFile 2s->5s
 - ProcessRetranslation 10ms->500ms
 - explicitly sync db backup to non-volatile memory only on reset/low-power.
 
- [06.11.2015]
 
- IEC-101/104 QOC (Qualifier of command) implementation (#2495)
 
- [05.11.2015]
 
- AI scaling rewrite (COMPATIBILITY BREAK)
 - virtual I/O object pair crash app if invalid address fix (#2572)
 
- [30.10.2015]
 
- web-server v2 shows device eth info (#2532)
 
- [16.10.2015]
 
- fix SPA-Bus polling delay (#2546)
 
- [14.10.2015]
 
- IEC DO_FN | IEC101/104 type 105 C_RP_NA_1 (reset process) implementation (#2498)
 - IEC DO_FN | IEC101/104 GI command via DO implementation (#2499)
 
- [13.10.2015]
 
- zero value deadband implementation (#2536)
 
- [24.09.2015]
 
- DO/AO stops IEC-101 messages fix for devices using old database (#2527)
 - allow bigger conf size for NEW_DATABASE devices
 - SETUP_WITH_XML_BIN_SIZE 500KB->1.5MB
 - EXTRACTED_XML_SETUP_SIZE 6MB->20MB
 
- [07.09.2015]
 
- GWM IO-board + 101-104 conversion not working fix (#2520)
 
- [25.08.2015]
 
- IEC-61850 mem-leak/consumption fixes
 - remove BIT_INVALID_TIME from BIT_VALUE_CHANGED_MASK
 
- [22.08.2015]
 
- devie booting time nnX times faster (#2472)
 
kernel 4 Changelog since 2017
- 2017.08.22
 
- fix GW DNS service
 
- 2017.02.10
 
- fix sftp access
 - fix configuring SSH from GWS
 
kernel 2 Changelog since 2013
- 2017.07.12
 
- log4cxx | patch for socket appender
 - pack_logs | pack modem history log
 - init | fix spamming logs (S48, S61m S99)
 - fw_update | fix errors on fw update (S12usb)
 - init | fix spamming logs on stop (S37)
 - modem | fix handling huawei modems
 - WebServer | Restore syslog options
 
- 2017.04.17-next-08-af772c0
 
- update | Additional checks in post-update scripts for GWM rev.1 FTDI IO Board
 
- 2017.04.05-next-07-65a2e5a
 
- pack_logs now packs all existing console logs and eeprom log if exists
 
- 2017.04.03-next-03-49423a0
 
- fix enabling peripheral power on startup with usbs suspended (fixes old GWM53 FTDI IO Board)
 
- 2017.01.31-next-01-3eefdf3
 
- remove cifs support from vmx25 kernel. No more space left on device.
 
- 2016.11.04-next-01-51a8c40 Don't use on VMX25 Don't use on GWM with DO
 
- IEC-101,104 | DO invert fix sending ACK with inverted address
 - init | S99phy fix toggling LAN power and wait longer
 - init | fix starting modem then date is in the start of epoch (1970)
 - init | Script fixes for fresh device with linux default time
 
- 2016.10.19-next-09-3e89e79 Don't use on VMX25 Don't use on GWM with DO
 
- CIFS support in kernel for network mounts !! This change bricks VMX25. Removed from VMX25 after 30.01.2017
 
- 2016.10.08-next-01-c91481f
 
- init | optimizations for FTDI eeprom software
 - init | getwdbootmsg fixes
 - init | major refactoring. Performance & readability fixes
 
- 2016.10.03-next-02-1cb7e5f
 
- Syslog | Add possibility to change loglevel and remote server port
 - ntp | do not restart ntp if only gps is configured (2711)
 - ntp | avoid frequent ntp restarts by other scripts
 - modem | avoid frequent modem restart by multiple scripts (only 1 restart allowed per one minute).
 - modem | rewrite telit modem reseting as described in telit manual
 - init | fix socat sometimes creating /dev/tty* as ordinary file instead of letting modem driver to do it.
 - init | performance fixes
 
- 2016.07.28-next-06-3d426af
 
- Device CPU frequency lowered from 1.2GHz to 1.0GHz | Improved ssh key generation and license cheking
 
- [11.02.2016]
 
- physical interface checker script implementation
 
- [10.02.2016]
 
- ADDED LIB TO PROJECT: fastformat
 
- [26.01.2016]
 
- GWS 'Get logs' acquires n+1 more rotating logs
 
- [23.07.2015]
 
- ADDED LIB TO PROJECT: boost_chrono to source.pro (websocketpp 0.6.0 depends)
 
- [08.06.2015]
 
- application segmentation fault fix (2429)
 
- [27.04.2015]
 
- DI fallback bug fix (2312)
 
- [23.04.2015]
 
- DI object double inversion bug fix (2345)
 
- [21.04.2015]
 
- no flags not working fix (2194)
 
- [24.03.2015]
 
- Periodical GI implementation for all protocols (every 5th minute of hour)
 
- [16.03.2015]
 
- Telem Master protocol implementation
 
- [29.01.2015]
 
- IEC-10x ASDU transfer implementation
 
- [30.10.2014]
 
- IEC-101B serial communication improvements
 
- [23.10.2014]
 
- No main/CSV log for individual objects
 
- 2014.01.13-next-01-2a5df30
 
- added uINT16 (unsigned 16bit integer) in modbus protocol. (also update gws)
 
- 2014.01.09-next-01-2fae2d9
 
- fix IEC104 bug in GW6
 
- 2014.01.07-next-01-8180155
 
- fix fallback (GW6e and GWM), "NONE" protocol, device "in use"=no, FP-to-normalised conversion, deadband issues, IEC104 bug in GW6e. (also update gws)
 
- 2013.11.18-next-04
 
- fix IEC-104 bug (mark data as NT if connection to IEC-104 slave is lost and parameter "failed query count for disabling contr." > 1)
 
- 2013.11.12-next01
 
- fix AO feedback bug in GW6 and RTA-A
 
- 2013.11.04-next
 
- time invalid flag for GW6 and RTA-A (also requires DSP/RTC software update!)
 
- 2013.10.24-next
 
- IEC101-to-IEC104 short time to long time conversion
 
- 2013.09.16-next07
 
- configurable COT=2 Bytes for IEC101b
 
- 2013.09.09-next01
 
- configurable COT=2 Bytes for IEC101ub
 
- 2013.07.12-next02
 
- write modem status to /var/log/modem.st
 
Old Devices RTA-A and GW6
Latest Firmware
Last fw version GW6: 2015.12.11-develop-01-104a492
Last fw version RTA-A M502: 2015.12.11-develop-01-104a492
Last fw version RTA-A M501: 2015.12.11-develop-01-104a492
GW6-1206
- Timezones for ports and system.
 
Userland
- dnsmasq
 - iperf
 
Kernel
- iptables: Support for -m limit. For instance:
 
/usr/sbin/iptables -t filter -A INPUT -p tcp --dport 2404 --sport 1024:65535 -m state --state NEW -m limit --limit 25/minute --limit-burst 100 -j ACCEPT
- tc: Basic support. For instance:
 
/sbin/tc qdisc del dev eth0 root 2> /dev/null > /dev/null /sbin/tc qdisc del dev eth0 ingress 2> /dev/null > /dev/null /sbin/tc qdisc add dev eth0 handle ffff: ingress /sbin/tc filter add dev eth0 parent ffff: protocol ip prio 1 u32 match ip src 0.0.0.0/0 police rate 512kbit burst 1m drop flowid :1 /sbin/tc qdisc add dev eth0 root handle 1: cbq avpkt 1000 bandwidth 20mbit /sbin/tc class add dev eth0 parent 1: classid 1:1 cbq rate 512kbit allot 1500 prio 1 bounded isolated /sbin/tc class add dev eth0 parent 1: classid 1:2 cbq rate 512kbit allot 1500 prio 2 bounded isolated /sbin/tc class add dev eth0 parent 1: classid 1:3 cbq rate 512kbit allot 1500 prio 3 bounded isolated /sbin/tc filter add dev eth0 parent 1: protocol ip prio 16 u32 match ip protocol 1 0xff flowid 1:1 /sbin/tc filter add dev eth0 parent 1: protocol ip prio 1 u32 match ip sport 80 0xffff flowid 1:2 /sbin/tc filter add dev eth0 parent 1: protocol ip prio 1 u32 match ip sport 22 0xffff flowid 1:3
GW6-1204
- IEC104: Respond to message sent to broadcast ASDU (0xFFFF)
 - IEC-62056: mask incoming data with 0x7F (ASCII protocol)
 - Serial ports: Suppress echo
 - WebPage: Long awaited by all interenet browsers the favicon.ico
 
GW6-1202
- IEC104: Fix possible event loss on ethernet cable removal.
 - Formula: Do not generate control event, on first successful calculation.
 
GW6-1200
- Firmware version readable through internal WebServer
 - Fix possible event loss when lots of changes arrive for one input.
 - GPRS-modem protocol: if connection to internet is lost, all TCP client connections are closed
 - IEC104: force long-time format
 
GW6-1198
- IEC101/103 Unbalanced Master: add feature polling delay
 - When sending a control operation over IEC103 channel with many devices. Speed up receiving of control response.
 
GW6-1196
- Connection loss with RTC-board does not result in watchdog reset.
- Symptoms: device will reset after 20 seconds of running.
 
 - Device will write system boot count and application start count to console.log. Latest values can be found in /var/local/telem/stats
 
RTA-A-1192
- RTA-A: possible to define DO object to clear annunciator LED 's
 - Modbus Master: Fix receiving of negative 16bit normalized values.
 
GW6-1190
- Added new update pack type app-only.
- Note: This update pack type should only be used on device with SW version 1190 or later.
 - This update will not overwrite system files - less chance for bricking if something goes wrong (accidental power loss or reset).
 
 - Generate /etc/network/interfaces file once after receiving new setup.
 - New protocol type IEC ^ Setup
- Only reading and writing of device setup is allowed on this Port.
 - Allows faster booting of device with a lot of unused Up-channel ports.