Check the version of the Telem-GW6Lin board, if is not the one needed. Update. | |||
Guide is here: [[GW6Lin software upgrade]] | |||
= | ==Updating Telem-RTC Board Firmware== | ||
<strike>Check the version of the Telem-RTC, if is not the one needed.</strike>(Not possible). Update | |||
#Erase Flash from the Controller | |||
# | ##Connect power supply to the device | ||
# | ##Switch ER to ON state. | ||
# | ##Wait 5 seconds | ||
# | ##Switch RST to ON state | ||
# | ##Switch ER to OFF state | ||
# | ##Switch PG to ON state | ||
## | ##Switch RST to OFF state | ||
## | ##Wait 10 seconds | ||
== | ##Switch RST to ON state | ||
# | ##Switch PG to OFF state | ||
# | ##Switch RST to OFF state | ||
# Load | ##The device is now ready for loading a new frame program | ||
# | #To Load a New Frame Program | ||
# | ##Extract Firmware files (Provided by Martem AS) to your computer | ||
# | ##Install “AT91 In-system Programmer” running “Install AT91-ISP v.13.exe” | ||
# | ##Specify paths to SAM-BA and bin files in “programmer.bat” file. For instance: | ||
###echo Setting path to SAM-BA path="C:\Program Files\ATMEL Corporation\AT91-ISP v1.13\sam-ba v2.9";%path% | |||
###echo Setting path to user files path="D:\Projects\RTU_ARM\RTU-T Firmware\V5";%path% | |||
##Specify the COM port. For instance if using COM 5 port: set COMIF=COM5 | |||
##Specify the COM port. For instance if using COM 5 port: set COMIF=COM5 | |||
##Run “gw6_rtc_programming.bat”(Switches ERASE and PROG have to be in OFF state ) | |||
##Wait until loading completing green colored message appears | |||
##Set default settings by switching.: switch RST ON/OFF state | |||
=Testing Telem-GW6 Ports= | |||
#Connect the PC to the Telem GW6 through port 2 RS232, load and writte the Test Configuration Setup "testgw6_3.csv" | |||
## Z:\Taimar\1.Test\GW6_allports | |||
#Connect the cables following this scheme | |||
##Ethernet to network | |||
##Port 1-RS422 to Port 5-RS422/485 | |||
##Port 2-RS232 to Port 10 | |||
##Port 3-RS232 to Port 6 | |||
##Port 4 Fiber optic to an external Fibreoptic Modem alredy connected to another device to check the communications. | |||
##Port 7 to Port 11 | |||
##Port 8 to Port 12 | |||
##Port 9 to Port 13 | |||
##GPS port to an external GPS device. | |||
#Check that all the leds are blinking | |||
#Open TDC, export IEC objects from Z:\Taimar\1.Test\GW6_allports\objects.csv and check IEC obj. all 7 BI-s must have value 1.(or 0 in IEC.exe) | |||
=Testing Internal Clock= | |||
#Change the time in the PC | |||
#Go to TDC, GW6 Setup, Common, Time Settings and make sure that the Enable GPS is not click. | |||
#Go to TDC, Settings and click on Gen. Int. + Time Sync. | |||
#Power ON/OFF (Wait until it restarts) | |||
#Open Putty | |||
##Load saved session "GW6-Timetest" and open (It will log on as martem user automatically, It will give you the time once you have type the password) // if there is no "GW6-Timetest" use IP 10.0.0.144 user: martem and once logged in, enter command: date | |||
##Password: Xooviet0 | |||
#The time should macht with the PCs time.//if not(like 1 jan 2000 0:xx:xx), start from 4 again(power on/off) | |||
=Testing GPS= | |||
#Go to TDC, GW6 Setup, Common, Time Settings and Enable GPS (Optical). Writte the new configuration on the Device. | |||
#Check the GPS green led is blinking. | |||
#Power ON/OFF (Wait until it restarts) | |||
##Load saved session "GW6-Timetest" and open (It will log on as martem user automatically, It will give you the time once you have type the password) | |||
##Password: Xooviet0 | |||
#The time now should macht the real time.//if not, ask for date couple of times again, GPS sync might take some time. |
Revision as of 09:07, 20 June 2011
Firmware Update
Telem-GW6lin Board Update
Check the version of the Telem-GW6Lin board, if is not the one needed. Update.
Guide is here: GW6Lin software upgrade
Updating Telem-RTC Board Firmware
Check the version of the Telem-RTC, if is not the one needed.(Not possible). Update
- Erase Flash from the Controller
- Connect power supply to the device
- Switch ER to ON state.
- Wait 5 seconds
- Switch RST to ON state
- Switch ER to OFF state
- Switch PG to ON state
- Switch RST to OFF state
- Wait 10 seconds
- Switch RST to ON state
- Switch PG to OFF state
- Switch RST to OFF state
- The device is now ready for loading a new frame program
- To Load a New Frame Program
- Extract Firmware files (Provided by Martem AS) to your computer
- Install “AT91 In-system Programmer” running “Install AT91-ISP v.13.exe”
- Specify paths to SAM-BA and bin files in “programmer.bat” file. For instance:
- echo Setting path to SAM-BA path="C:\Program Files\ATMEL Corporation\AT91-ISP v1.13\sam-ba v2.9";%path%
- echo Setting path to user files path="D:\Projects\RTU_ARM\RTU-T Firmware\V5";%path%
- Specify the COM port. For instance if using COM 5 port: set COMIF=COM5
- Specify the COM port. For instance if using COM 5 port: set COMIF=COM5
- Run “gw6_rtc_programming.bat”(Switches ERASE and PROG have to be in OFF state )
- Wait until loading completing green colored message appears
- Set default settings by switching.: switch RST ON/OFF state
Testing Telem-GW6 Ports
- Connect the PC to the Telem GW6 through port 2 RS232, load and writte the Test Configuration Setup "testgw6_3.csv"
- Z:\Taimar\1.Test\GW6_allports
- Connect the cables following this scheme
- Ethernet to network
- Port 1-RS422 to Port 5-RS422/485
- Port 2-RS232 to Port 10
- Port 3-RS232 to Port 6
- Port 4 Fiber optic to an external Fibreoptic Modem alredy connected to another device to check the communications.
- Port 7 to Port 11
- Port 8 to Port 12
- Port 9 to Port 13
- GPS port to an external GPS device.
- Check that all the leds are blinking
- Open TDC, export IEC objects from Z:\Taimar\1.Test\GW6_allports\objects.csv and check IEC obj. all 7 BI-s must have value 1.(or 0 in IEC.exe)
Testing Internal Clock
- Change the time in the PC
- Go to TDC, GW6 Setup, Common, Time Settings and make sure that the Enable GPS is not click.
- Go to TDC, Settings and click on Gen. Int. + Time Sync.
- Power ON/OFF (Wait until it restarts)
- Open Putty
- Load saved session "GW6-Timetest" and open (It will log on as martem user automatically, It will give you the time once you have type the password) // if there is no "GW6-Timetest" use IP 10.0.0.144 user: martem and once logged in, enter command: date
- Password: Xooviet0
- The time should macht with the PCs time.//if not(like 1 jan 2000 0:xx:xx), start from 4 again(power on/off)
Testing GPS
- Go to TDC, GW6 Setup, Common, Time Settings and Enable GPS (Optical). Writte the new configuration on the Device.
- Check the GPS green led is blinking.
- Power ON/OFF (Wait until it restarts)
- Load saved session "GW6-Timetest" and open (It will log on as martem user automatically, It will give you the time once you have type the password)
- Password: Xooviet0
- The time now should macht the real time.//if not, ask for date couple of times again, GPS sync might take some time.