This element contains: | This element contains: | ||
*Element: '''Channel''' | *Element: '''[[Gw_XML_setup#Element:_Channel | Channel]]''' | ||
*Element: '''Protocol''' | *Element: '''[[Gw_XML_setup#Element:_Protocol | Protocol]]''' | ||
*Element: '''Objects''' | *Element: '''[[Gw_XML_setup#Element:_Objects | Objects]]''' | ||
*Element: '''Interfaces''' | *Element: '''[[Gw_XML_setup#Element:_Interfaces | Interfaces]]''' | ||
*Attribute: '''id''' | *Attribute: '''id''' | ||
** Used for element identification | ** Used for element identification | ||
Line 22: | Line 22: | ||
== Element: Channel == | == Element: Channel == | ||
This element contains: | This element contains: | ||
*Element: '''Port''' | *Element: '''[[Gw_XML_setup#Element:_Port | Port]]''' | ||
*Element: '''Device''' | *Element: '''[[Gw_XML_setup#Element:_Device | Device]]''' | ||
*Element: '''Objects''' | *Element: '''[[Gw_XML_setup#Element:_Objects | Objects]]''' | ||
== Element: Protocol == | == Element: Protocol == | ||
== Element: Port == | == Element: Port == |
Revision as of 15:57, 16 May 2011
Element: Setup
The XML setup starts with the tag Setup. The entire setup is contained in this element.
<Setup />
This element contains:
- Element: Device
- At least one element of this type.
- Attribute: device
- If more than one Device element available. This attribute specifies the id of the Device to use as current setup.
Element: Device
This element contains setup for a specific device. This might be Gw itself or some substation device or SCADA device.
This element contains:
- Element: Channel
- Element: Protocol
- Element: Objects
- Element: Interfaces
- Attribute: id
- Used for element identification
Element: Channel
This element contains:
Element: Protocol
Element: Port
Serial port
<Port class="SerialPortSetup"> <BaudRate>9600</BaudRate> <DataBits>8</DataBits> <StopBits>1</StopBits> <Parity>none</Parity> <FlowControl>none</FlowControl> </Port>
TCP/IP server
<Port class="TcpIpServerSetup"> <PortNumber>80</PortNumber> <ClientIpMask>0.0.0.0</ClientIpMask> <Interface>eth0</Interface> </Port>
TCP/IP client
<Port class="TcpIpClientSetup" name="16"> <PortNumber>502</PortNumber> <IpAddress>10.0.0.89</IpAddress> <Interface>eth0</Interface> </Port>
Virtual port
They are ports 3-5 on GW6.
<Port class="VirtualPortSetup"> <Port class="SerialPortSetup"> <BaudRate>9600</BaudRate> <DataBits>8</DataBits> <StopBits>1</StopBits> <Parity>none</Parity> <FlowControl>none</FlowControl> </Port> </Port>
Element: Objects
Element: Interfaces
Network setup
Has at least one Interface element.
<Interface name="eth0"> <IpAddress>192.168.0.111</IpAddress> <Netmask>255.255.255.0</Netmask> <Gateway>192.168.0.1</Gateway> </Interface>