GW6e Conformance Test: Difference between revisions
Jump to navigation
Jump to search
mNo edit summary |
No edit summary |
||
Line 19: | Line 19: | ||
! Transmission speed | ! Transmission speed | ||
|- | |- | ||
| 1200 bit/s || align="center" | | | 1200 bit/s || align="center" | OK | ||
| 2400 bit/s || align="center" | OK | |||
| 2400 bit/s || align="center" | | |||
|- | |- | ||
| 4800 bit/s || align="center" | OK | | 4800 bit/s || align="center" | OK |
Revision as of 16:23, 23 October 2013
GW6e Conformance Test
NAME | STATUS | ||
---|---|---|---|
Implemented transmission system | |||
Unbalanced system | OK | ||
Network configuration | |||
Point-to-point | OK | ||
Multidrop | OK | ||
PHYSICAL LAYER | |||
Transmission speed | |||
1200 bit/s | OK | 2400 bit/s | OK |
4800 bit/s | OK | ||
9600 bit/s | OK | ||
19200 bit/s | OK | ||
LINK LAYER | |||
Link transmission procedure | |||
Unbalanced transmission | OK | ||
Address field of the link | |||
One octet | OK | ||
Two octets | OK | ||
Frame length | |||
Unstructured | OK | ||
Common address of ASDU | |||
One octet | OK | ||
Information object address | |||
Two octets | OK | ||
Three octets | OK | ||
Unstructured | - | ||
Cause of transmission | |||
One octet | OK | ||
SELECTION OF STANDARD ASDUS | |||
Process information in monitor direction | |||
<1> := Single-point information M_SP_NA_1 | OK | ||
<2> := Single-point information with time tag M_SP_TA_1 | OK | ||
<3> := Double-point information M_DP_NA_1 | OK | ||
<4> := Double-point information with time tag M_DP_TA_1 | OK | ||
<5> := Step position information M_ST_NA_1 | OK | ||
<6> := Step position information with time tag M_ST_TA_1 | OK | ||
<9> := Measured value, normalised value M_ME_NA_1 | OK | ||
<10> := Measured value, normalised value with time tag M_ME_TA_1 | OK | ||
<11> := Measured value, scaled value M_ME_NB_1 | OK | ||
<12> := Measured value, scaled value with time tag M_ME_TB_1 | OK | ||
<13> := Measured value, short floating point value M_ME_NC_1 | OK | ||
<14> := Measured value, short floating point value with time tag M_ME_TC_1 | OK | ||
<30> := Single point information with full time M_SP_TB_1 | OK | ||
<31> := Double point information with full time M_DP_TB_1 | OK | ||
<32> := Step position information with full time M_ST_TB_1 | OK | ||
<34> := Measured value, normalised value with full time M_ME_TD_1 | OK | ||
<35> := Measured value, scaled value with full time M_ME_TE_1 | OK | ||
<36> := Measured value, short floating point value with full time M_ME_TF_1 | OK | ||
Process information in control direction | |||
<45> := Single command C_SC_NA_1 | OK | ||
<46> := Double command C_DC_NA_1 | OK | ||
<47> := Regulating step command C_RC_NA_1 | X | ||
<58> := Single command with time tag CP56Time 2a C_SC_TA_1 | X | ||
<59> := Double command with time tag CP56Time 2a C_DC_TA_1 | X | ||
<60> := Regulating step command with time tag CP56Time 2a C_RC_TA_1 | X | ||
System information in monitor direction | |||
<70> := End of initialisation M_EI_NA_1 | OK | ||
System information in control direction | |||
<100> := Interrogation command C_IC_NA_1 | OK | ||
<102> := Read command C_RD_NA_1 | X | ||
<103> := Clock synchronisation command C_CS_NA_1 | OK | ||
<105> := Reset process command C_RP_NC_1 | OK | ||
<106> := Delay acquisition command C_CD_NA_1 | OK | ||
File Transfer | |||
<120> := File ready F_FR_NA_1 | X | ||
<121> := Section ready F_SR_NA_1 | X | ||
<122> := Call directory, select file, call file, call section F_SC_NA_1 | X | ||
<123> := Last section, last segment F_LS_NA_1 | X | ||
<124> := Ack file, ack section F_AF_NA_1 | X | ||
<125> := Segment F_SG_NA_1 | X | ||
<126> := Directory F_DR_TA_1 | X | ||
BASIC APPLICATION FUNCTIONS | |||
Station Initialisation | |||
Station initialisation for unbalanced systems | - | ||
Remote initialisation | - | ||
Data acquisition by polling | |||
first procedure: “request user data class 1”. | - | ||
second procedure: “request user data class 2”. | - | ||
Read procedure | |||
for Unbalanced systems C_RD_DATA | - | ||
Cyclic data transmission | |||
cyclic data transmission | - | ||
Acquisition of events (for unbalanced systems) | |||
case 1: spontaneous data is NOT available | - | ||
case 2: spontaneous data is available | - | ||
General Interrogation | |||
Interrogation procedure for unbalanced systems | OK | ||
Interrogation procedure for events arrive between interrogation responses | - | ||
Global | OK | ||
group 1 | OK | ||
group 2 | OK | ||
Clock synchronisation | |||
Clock synchronisation for unbalanced systems | OK | ||
Command transmission | |||
Command procedure for unbalanced systems | - | ||
Direct single command transmission | - | ||
Direct double command transmission | - | ||
Direct regulation command transmission | - | ||
Select and execute single command | - | ||
Select and execute double command | - | ||
Select and execute regulation command | - | ||
ACTTERM is used | - | ||
No additional definition | - | ||
Short pulse duration (duration determined by a system parameter in the outstation) | - | ||
Long pulse duration (duration determined by a system parameter in the outstation) | - | ||
Persistent output | - | ||
File transfer | |||
File transfer in monitor direction | X | ||
File transfer in control direction | X | ||
Acquisition of transmission delay | |||
Acquisition transmission delay | - |
Type identification | Cause of transmission | ||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 20-36 | 37-40 | 44 | 45 | 46 | 47 | |
<1> M_SP_NA_1 | |||||||||||||||||||
<2> M_SP_TA_1 | |||||||||||||||||||
<3> M_DP_NA_1 | |||||||||||||||||||
<4> M_DP_TA_1 | |||||||||||||||||||
<5> M_ST_NA_1 | |||||||||||||||||||
<6> M_ST_TA_1 | |||||||||||||||||||
<7> M_BO_NA_1 | |||||||||||||||||||
<8> M_BO_TA_1 | |||||||||||||||||||
<9> M_ME_NA_1 | |||||||||||||||||||
<10> M_ME_TA_1 | |||||||||||||||||||
<11> M_ME_NB_1 | |||||||||||||||||||
<12> M_ME_TB_1 | |||||||||||||||||||
<13> M_ME_NC_1 | |||||||||||||||||||
<14> M_ME_TC_1 | |||||||||||||||||||
<15> M_IT_NA_1 | |||||||||||||||||||
<16> M_IT_TA_1 | |||||||||||||||||||
<17> M_EP_TA_1 | |||||||||||||||||||
<18> M_EP_TB_1 | |||||||||||||||||||
<19> M_EP_TC_1 | |||||||||||||||||||
<20> M_PS_NA_1 | |||||||||||||||||||
<21> M_ME_ND_1 | |||||||||||||||||||
<30> M_SP_TB_1 | |||||||||||||||||||
<31> M_DP_TB_1 | |||||||||||||||||||
<32> M_ST_TB_1 | |||||||||||||||||||
<33> M_BO_TB_1 | |||||||||||||||||||
<34> M_ME_TD_1 | |||||||||||||||||||
<35> M_ME_TE_1 | |||||||||||||||||||
<36> M_ME_TF_1 | |||||||||||||||||||
<37> M_IT_TB_1 | |||||||||||||||||||
<38> M_EP_TD_1 | |||||||||||||||||||
<39> M_EP_TE_1 | |||||||||||||||||||
<40> M_EP_TF_1 | |||||||||||||||||||
<45> C_SC_NA_1 | |||||||||||||||||||
<46> C_DC_NA_1 | |||||||||||||||||||
<47> C_RC_NA_1 | |||||||||||||||||||
<48> C_SE_NA_1 | |||||||||||||||||||
<49> C_SE_NB_1 | |||||||||||||||||||
<50> C_SE_NC_1 | |||||||||||||||||||
<51> C_BO_NA_1 | |||||||||||||||||||
<58> C_SC_TA_1 | |||||||||||||||||||
<59> C_DC_TA_1 | |||||||||||||||||||
<60> C_RC_TA_1 | |||||||||||||||||||
<61> C_SE_TA_1 | |||||||||||||||||||
<62> C_SE_TB_1 | |||||||||||||||||||
<63> C_SE_TC_1 | |||||||||||||||||||
<64> C_BO_TA_1 | |||||||||||||||||||
<70> M_EI_NA_1 | |||||||||||||||||||
<100> C_IC_NA_1 | |||||||||||||||||||
<101> C_CI_NA_1 | |||||||||||||||||||
<102> C_RD_NA_1 | |||||||||||||||||||
<103> C_CS_NA_1 | |||||||||||||||||||
<104> C_TS_NA_1 | |||||||||||||||||||
<105> C_RP_NA_1 | |||||||||||||||||||
<106> C_CD_NA_1 | |||||||||||||||||||
<110> P_ME_NA_1 | |||||||||||||||||||
<111> P_ME_NB_1 | |||||||||||||||||||
<112> P_ME_NC_1 | |||||||||||||||||||
<113> P_AC_NA_1 | |||||||||||||||||||
<120> F_FR_NA_1 | |||||||||||||||||||
<121> F_SR_NA_1 | |||||||||||||||||||
<122> F_SC_NA_1 | |||||||||||||||||||
<123> F_LS_NA_1 | |||||||||||||||||||
<124> F_AF_NA_1 | |||||||||||||||||||
<125> F_SG_NA_1 | |||||||||||||||||||
<126> F_DR_TA_1 |