Actaris ACE6000: Difference between revisions

From Phobos Wiki
Jump to navigation Jump to search
No edit summary
Line 11: Line 11:
More than '''1500'''ms
More than '''1500'''ms
==Objects tab==
==Objects tab==
Lower level object address for '''Reactive energy import''' is '''380'''
Enter the object's address to column named "61850 v"


Lower level object address for '''Energy rate 02''' is '''182'''
===Examples===


You can see the address in the picture under code column.
Address for '''Reactive energy import''' is '''3.8.0'''
Address for '''Energy rate 02''' is '''1.8.2'''
Address could even be '''C.55.6'''  or '''FF.FF.2'''
 
You can see the address in the picture under the column '''code'''.


=Aims Pro=
=Aims Pro=

Revision as of 16:12, 16 September 2010

GWS

Ports tab

Communication parameters

  • Parity: EVEN
  • Stop bits: 1
  • Data bits: 7

Polling delay

  • One device per channel: 0ms - unlimited
  • 2 or more devices per channel: 2000ms - unlimited

Query timeout

More than 1500ms

Objects tab

Enter the object's address to column named "61850 v"

Examples

Address for Reactive energy import is 3.8.0
Address for Energy rate 02 is 1.8.2
Address could even be C.55.6  or FF.FF.2

You can see the address in the picture under the column code.

Aims Pro

Display tab in ACE6000 configuration program

Pilt:ACE6000_Aims_Pro_Display_page.jpg