Firmware Update
Telem-GW6lin Board Update
Check the version of the Telem-GW6Lin board, if is not the one needed. Update.
Guide is here: GW6Lin software upgrade
Updating Telem-RTC Board Firmware
Check the version of the Telem-RTC, if is not the one needed.(Not possible). Update
- Erase Flash from the Controller
- Connect power supply to the device
- Switch ER to ON state.
- Wait 5 seconds
- Switch RST to ON state
- Switch ER to OFF state
- Switch PG to ON state
- Switch RST to OFF state
- Wait 10 seconds
- Switch RST to ON state
- Switch PG to OFF state
- Switch RST to OFF state
- The device is now ready for loading a new frame program
- To Load a New Frame Program
- Extract Firmware files (Provided by Martem AS) to your computer
- Install “AT91 In-system Programmer” running “Install AT91-ISP v.13.exe”
- Specify paths to SAM-BA and bin files in “programmer.bat” file. For instance:
- echo Setting path to SAM-BA path="C:\Program Files\ATMEL Corporation\AT91-ISP v1.13\sam-ba v2.9";%path%
- echo Setting path to user files path="D:\Projects\RTU_ARM\RTU-T Firmware\V5";%path%
- Specify the COM port. For instance if using COM 5 port: set COMIF=COM5
- Specify the COM port. For instance if using COM 5 port: set COMIF=COM5
- Run “gw6_rtc_programming.bat”(Switches ERASE and PROG have to be in OFF state )
- Wait until loading completing green colored message appears
- Set default settings by switching.: switch RST ON/OFF state
Testing Telem-GW6 Ports
- Connect the PC to the Telem GW6 through port 2 RS232, load and writte the Test Configuration Setup "testgw6_3.csv"
- Z:\Taimar\1.Test\GW6_allports
- Connect the cables following this scheme
- Ethernet to network
- Port 1-RS422 to Port 5-RS422/485
- Port 2-RS232 to Port 10
- Port 3-RS232 to Port 6
- Port 4 Fiber optic to an external Fibreoptic Modem alredy connected to another device to check the communications.
- Port 7 to Port 11
- Port 8 to Port 12
- Port 9 to Port 13
- GPS port to an external GPS device.
- Check that all the leds are blinking
- Open TDC, export IEC objects from Z:\Taimar\1.Test\GW6_allports\objects.csv and check IEC obj. all 7 BI-s must have value 1.(or 0 in IEC.exe)
Testing Internal Clock
- Change the time in the PC
- Go to TDC, GW6 Setup, Common, Time Settings and make sure that the Enable GPS is not click.
- Go to TDC, Settings and click on Gen. Int. + Time Sync.
- Power ON/OFF (Wait until it restarts)
- Open Putty
- Load saved session "GW6-Timetest" and open (It will log on as martem user automatically, It will give you the time once you have type the password) // if there is no "GW6-Timetest" use IP 10.0.0.144 user: martem and once logged in, enter command: date
- Password: Xooviet0
- The time should macht with the PCs time.//if not(like 1 jan 2000 0:xx:xx), start from 4 again(power on/off)
Testing GPS
- Go to TDC, GW6 Setup, Common, Time Settings and Enable GPS (Optical). Writte the new configuration on the Device.
- Check the GPS green led is blinking.
- Power ON/OFF (Wait until it restarts)
- Load saved session "GW6-Timetest" and open (It will log on as martem user automatically, It will give you the time once you have type the password)
- Password: Xooviet0