Basic command-line

From Phobos Wiki
Revision as of 08:56, 3 March 2015 by Alfred (talk | contribs)
Jump to navigation Jump to search

Basic

  • Log in as super user
su
  • Display current software and hardware version
cat /VERSION
  • Uptime of system
uptime
  • Display product name
 cat /usr/local/etc/telem/product 
  • Display product ID
 cat /usr/local/etc/telem/product_id 
  • Display product order code
 cat /usr/local/etc/telem/order_code
  • Display product processor type
cat /proc/cpuinfo
  • Free storage on system
df -h

Time & GPS

  • Show system time
date
  • Show time from hardware clock (UTC)
hwclock -r
  • Manually set system time to 30.november 2015, 17:00 and reboot (date format MMDDhhmm[[YY]YY][.ss])
su -c "date 113017002015;hwclock -w -u;reboot" 
  • Monitor data received from GPS connected to C1 (or Com1 for GWM). More details: GPS in port C1
cat /dev/gps0
  • Monitor PPS pulse received from GPS connected to C1 (or Com1 for GWM). More details: GPS in port C1
ppswatch -a /dev/gpspps0

Logs & files

  • Display content of console.log
cat /var/log/telem/console.log
  • Follow the content of console.log
tail -f /var/log/telem/console.log
  • Follow the content of console.log, only show lines containing phrase "DI23"
tail -f /var/log/telem/console.log |grep DI23
  • Save a TCP capture log from eth2, TCP port 2404, to file tcplog1.pcap (Wireshark compatible)
tcpdump -i eth2 -n  tcp port 2404 -w tcplog1.pcap
  • Edit the file named log-conf.xml (changes will be lost after reboot)
 nano /usr/local/etc/telem/log-conf.xml

Configs

  • List old GWS configs available
/etc/init.d/S11telem-config list-old
  • Load old GWS configs number 3
/etc/init.d/S11telem-config old 3 

Application statistics