IEC101 Objects
Jump to navigation
Jump to search
For all addresses the GWS parameter "Objects Base Address" is 0.
Setup file for iex.exe can be found from \\Phobos\d\3_Tehniline\3.Seadmed\RTU_T\TELEM-AI12-T Objects.csv(Latest version svn://phobos.martem.ee/RTU-T-AI12/doc/TestObjectsForIecExe.csv)
Address | Description | Default Value |
---|---|---|
1 ... 12 | Input 1 ... 12 result after zero zone and deadband1 | Unknown |
50 | ZERO ZONE ENABLE - turns zero zone calculation ON or OFF | ON |
51 | DEADBAND1 ENABLE - turns deadband1 calculation ON or OFF | ON |
100 | CAL DATA GI - turns sending of calibration data ON or OFF on GI | OFF |
101 ... 112 | CHx OFFSET - Channel x offset, in ADC digits | Unknown |
113 ... 124 | CHx REF - Channel x reference, in ADC digits | Unknown |
200 | CORR ENABLE - turns ON or OFF all calculations of ADC input | ON |
1000 | LED RED - turns ON or OFF ALERT LED | OFF |
2000 | ENABLE DEBUG - turns ON or OFF sending of software debug parameters | OFF |
2001 | CLOCK TEST DI - Value is the state of synchronization selection(1 for internal RTC 0 for external signal), timestamp is the current time of TELEM-AI12 | Unknown |
2002 | ERROR DEADLINE - counter for task deadlines. If this value increases then TELEM-AI12 is not working correctly | 0 |
2003 | ERROR AD73360 - counter for ADC AD73360. If this value increases then AD73360 is not working correctly | 0 |
2004 | ERROR QUEUE AD73360 - counter for ADC AD73360 queue. If this value increases then AD73360 is not working correctly | 0 |
2005 | ERROR HZ - counter for syncronization errors. If this value increases then TELEM-AI12 has encountered syncronization signals that are much longer or shorter than 1 second. | 0 |
2006 | ERROR QUEUE DATA1 - counter for IEC101 Data Class1 queue. If this value increases then it is an indication of communication errors. | 0 |
2006 | ERROR SPONT CNT - counter for spontaneous events. If this value increases then it is an indication that some events are dropped. Indication of communication errors. | 0 |