Serial connection

From Phobos Wiki
Revision as of 09:42, 9 March 2015 by Roland (talk | contribs) (Uus lehekülg: 'Serial connection can be used with RTU-T modules, Telem AI-12T, Telem DI24-T, Telem DO5-T and older Telem devices like: RTA, RTA-A, GW5, GW6. <br /> Serial connection uses IEC 60...')
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search

Serial connection can be used with RTU-T modules, Telem AI-12T, Telem DI24-T, Telem DO5-T and older Telem devices like: RTA, RTA-A, GW5, GW6.
Serial connection uses IEC 60870-5-101 protocol. To establish connection corresponding parameters have to be set in the Device-> Communication Setup.

Network: Define network to use connecting with Telem device
Port: COM port of PC used for communication
GW6 USB interface: Not supported
Parity: Use of parity control bit (default: none)
Baud rate: Data communication rate (9600)
Link Address: link address of Telem device (1)
ASDU address: ASDU address of Telem device (1)
Status: Status of the connection. RED – no connection, GREEN – connection OK
Communication delay: Delay between reception of data and the next query in milliseconds (0)
ASDU address length: The length of the ASDU address in bytes: possible values are 1 or 2. (2)
Object address length: Length in bytes. Possible values are 1, 2 or 3. (2)