Modbus Martem
Jump to navigation
Jump to search
Addressing scheme
Introduction
Modbus addressing scheme is separated in to the address and the function code.
Address
Modbus addresses are extracted from GWS column 'Obj. Addr. v' in the following way:
if(100000 <= address) address %= 100000; else address %= 10000;
Function Code
Function Code enumeration
Telem Application Modbus function code enumeration:
enum ModbusFunctionCodes { MODBUS_FN_UNSUPPORTED = 0x0, MODBUS_READ_COIL = 0x1, MODBUS_READ_INPUT = 0x2, MODBUS_READ_HOLDING_REGISTERS = 0x3, MODBUS_READ_INPUT_REGISTERS = 0x4, MODBUS_FORCE_SINGLE_COIL = 0x5, MODBUS_SET_SINGLE_REGISTER = 0x6, MODBUS_FORCE_MULTIPLE_COIL = 0xF, MODBUS_SET_MULTIPLE_REGISTER = 0x10 };
Function code extracting has small differences for input and output objects in Telem Application.
Input objects
Input objects function code is determined from the address in the following way:
if(100000 <= address) fn_code = address / 100000; else fn_code = address / 10000; switch( fn_code ) { case 0: return MODBUS_READ_COIL; case 1: return MODBUS_READ_INPUT; case 3: return MODBUS_READ_INPUT_REGISTERS; default: case 4: return MODBUS_READ_HOLDING_REGISTERS; }
Digital output objects
Digital output function codes are determined by their 'SubType^' type in GWS:
if( SubType^ == Single ) { return MODBUS_FORCE_SINGLE_COIL } else { return MODBUS_FORCE_MULTIPLE_COIL }
Analog output objects
Analog output objects always use MODBUS_SET_SINGLE_REGISTER as function code.