IEC101 Objects

From Phobos Wiki
Revision as of 07:53, 25 October 2010 by 10.0.0.98 (talk)
Jump to navigation Jump to search

For all addresses the GWS parameter "Objects Base Address" is 0.

Setup file for iex.exe can be found from \\Phobos\d\3_Tehniline\3.Seadmed\RTU_T\TELEM-AI12-T Objects.csv(Latest version svn://phobos.martem.ee/RTU-T-AI12/doc/TestObjectsForIecExe.csv)


AddressDescriptionDefault Value
1 ... 12 Input 1 ... 12 result after zero zone and deadband1 Unknown
50 ZERO ZONE ENABLE - turns zero zone calculation ON or OFF ON
51 DEADBAND1 ENABLE - turns deadband1 calculation ON or OFF ON
100 CAL DATA GI - turns sending of calibration data ON or OFF on GI OFF
101 ... 112 CHx OFFSET - Channel x offset, in ADC digits Unknown
113 ... 124 CHx REF - Channel x reference, in ADC digits Unknown
125 ... 136 AIx OFFSET - AI x offset, in ADC digits. Can be different from CHx OFFSET if AIx is configured for voltage. For voltage a PGA is used. Unknown
200 CORR ENABLE - turns ON or OFF all calculations of ADC input ON
1000 LED RED - turns ON or OFF ALERT LED OFF
2000 ENABLE DEBUG - turns ON or OFF sending of software debug parameters. Debug parameters start with address 2001. OFF
2001 CLOCK TEST DI - Value is the state of synchronization selection(1 for internal RTC 0 for external signal), timestamp is the current time of TELEM-AI12 Unknown
2002 ERROR DEADLINE - counter for task deadlines. If this value increases then TELEM-AI12 is not working correctly 0
2003 ERROR AD73360 - counter for ADC AD73360. If this value increases then AD73360 is not working correctly 0
2004 ERROR QUEUE AD73360 - counter for ADC AD73360 queue. If this value increases then AD73360 is not working correctly 0
2005 ERROR HZ - counter for syncronization errors. If this value increases then TELEM-AI12 has encountered syncronization signals that are much longer or shorter than 1 second. 0
2006 ERROR QUEUE DATA1 - counter for IEC101 Data Class1 queue. If this value increases then it is an indication of communication errors. 0
2006 ERROR SPONT CNT - counter for spontaneous events. If this value increases then it is an indication that some events are dropped. Indication of communication errors. 0
2007 ERROR AI IO - AD73360 serial communication errors. In mixed mode 16th bit must me 0 0
2008 ERROR AI AVG - AD73360 input accumulator errors. Averaged channel result is larger than 16bits. 0
2009 ERROR AI MATH - input conversion and calibration errors from calculation. 0