Testimise juhend
1) Ühenda 1 pordi kaudu seade Telem-DI20G kontsentraator TELEM2000-ga. Seadme ja TELEM2000 vahel peab tekkima side.
2) Tee seadmele programmi kaudu reset3.
3) Anda kõikidesse sisenditesse sisendsignaal. Selleks lühistada sisendid. Kontrollida, kas IEC tabelis tekivad vastavad sündmused. Samal ajal jälgida, kas vastava sisendsignaali andmisel süttib ka indikaator-LED.
4) Ühenda 2. porti GPS interface ja kontolli kas GPS-aeg muudab kontrolleris aja.
5) Ühenda mitu kontrollerit järjestiku ja kontrolli, kas pordides 3 ja 4 tekib RS422 side.
6) Kanna jooksvalt saadud tulemused testimise protokolli.
Koostas: Meelis Osi