Telem-RTA-A
Jump to navigation
Jump to search
M501 Default Settings
Setting | default ver<1190 | ver>1190 | |
---|---|---|---|
Default IP | 192.168.2.127 | 192.168.0.111 | |
Netmask | 255.255.255.0 | 255.255.255.0 | |
Login | root | root | martem |
Password | root | reH3epea | Xooviet0 |
Software upgrades for Linux
- You can find the software here
- \\Phobos\d\3_Tehniline\Tarkvara myygiks\RTA-A
Updating
- Login with FTP
- If you're using a new M501 board, use the details above
- If it's a configured RTA-A then use the IP you have configured to the device.
- Copy all files except RtaMain to /disk/
- If it fails, try again.
- Copy RtaMain to /disk/
- If RTA-A resets during the copy process, you might need to use 192.168.2.127 as the FTP IP address
- Try again
- Allow execution permissions for these files
- /disk/gateway.sh
- /disk/RtaMain
- /disk/runfirst.sh
- Wait ~30 seconds, so everything is written to flash.
- Reset RTA-A
- Wait ~30 seconds until RTA-A starts, if not running by then, update failed.