Telem-app configuration
Feature
telem-app functionality can be tweaked via command line arguments and config files
Config file
The easiest way to add/override configuration options is to modify the /etc/telem-gw.user.conf file
This config file is checked by telem-app by default without any additional command line arguments
Enable Periodical GI with predefined time interval
Add the follown lines to /etc/telem-gw.user.conf:
protocol.periodical-gi.use-interval=1 protocol.periodical-gi.offset=00:02:00
This will indicate to telem-app that it should do a Periodical GI every 2 minutes instead of every hour at 00:05:00.
If protocol.periodical-gi.offset
is left out, then the default value of 00:05:00 is used.
If protocol.periodical-gi.use-interval
is not set, then Periodical GI is done every hour at value assigned to protocol.periodical-gi.offset
. E.g. in case of default 00:05:00 Periodical GI will be issued every hour at xx:05:00.
NB! This feature is available in firmware dating from 2017.09.05