Configuration of connected Telem RTU I/O modules remotely via data concentrator
Jump to navigation
Jump to search
Configuration Redirection is used to configure RTU-T modules via data concentrator using 101 or 104 connection.
Data concentrator has to have 101 or 104 port upwards configured to enable conf redirection.
Using that function all Telem RTU-T devices are configurable using ethernet connection.
It is recommended to create another port in the data concentrator configuration: IEC setup, if conf. redirection is needed.
Following steps should be followed:
- Create IEC setup port to configuration or use already active 101 or 104 up for establishing connection with data concentrator over ethernet.
- Create connection to data concentrator via 101 or 104 over Ethernet.
- From the Telem configurator window choose device-> communication setup
- Check use Network
- define protocol (101 or 104)
- Insert IP address of data concentrator (if IEC 104 is used)
- Insert TCP port number that is used
- Find out the device number (from devices tab card) You want to configure (e.g. device nr 1)
- Activate conf redirection using device number (from configuration, devices tab card).
- From the Telem configurator window choose device-> GW6/RTA-A conf. redirection.
Number in that window cannot be entered from keyboards (right-handed) num pad. Current window must be opened during configuration I/O module.
- Choose which type of module You want to configure.
- Read or Write configuration of I/O module.
Hint: If for example Telem-RTA-A is connected to GW6 (RTU) serial port as sub- RTU (one collects data from another),
then the configuration of RTA-A can be remotely read and written through the GW6 using the configuration program.