Configuration of connected Telem RTU I/O modules remotely via data concentrator

From Phobos Wiki
Jump to navigation Jump to search

Configuration Redirection is used to configure RTU-T modules via data concentrator using 101 or 104 connection.
Data concentrator has to have 101 or 104 port upwards configured to enable conf redirection.
Using that function all Telem RTU-T devices are configurable using ethernet connection.

It is recommended to create another port in the data concentrator configuration: IEC setup, if conf. redirection is needed.
Following steps should be followed:

  • Create IEC setup port to configuration or use already active 101 or 104 up for establishing connection with data concentrator over ethernet.
  • Create connection to data concentrator via 101 or 104 over Ethernet.
    • From the Telem configurator window choose device-> communication setup
    • Check use Network
    • define protocol (101 or 104)
    • Insert IP address of data concentrator (if IEC 104 is used)
    • Insert TCP port number that is used
  • Find out the device number (from devices tab card) You want to configure (e.g. device nr 1)
  • Activate conf redirection using device number (from configuration, devices tab card).
  • From the Telem configurator window choose device-> GW6/RTA-A conf. redirection.
Number in that window cannot be entered from keyboards (right-handed) num pad. Current window must be opened during configuration I/O module.
  • Choose which type of module You want to configure.
  • Read or Write configuration of I/O module.
Hint: If for example Telem-RTA-A is connected to GW6 (RTU) serial port as sub- RTU (one collects data from another), 
then the configuration of RTA-A can be remotely read and written through the GW6 using the configuration program.